top of page

LoRaWAN Fuel Flow Meter

SKU#
WSLRW-DFM
Replaced by
Replaced SKU
WSLRW-DFM is an advanced devices that use LoRaWAN (Low Power Wide Area Network) technology to measure and transmit fuel flow data over long distances. These meters are particularly useful for remote monitoring and management of fuel usage in various applications, such as industrial processes, fuel distribution, and storage. The meter provides real-time monitoring and optimization of fuel consumption, normalization of fuel quotas, detection and prevention of fuel theft, and fuel consumption testing for engines/genset. LoRaWAN fuel flow meters are used in various industries like manufacturing, agriculture, transportation, and smart cities. The device will transmit data in kilo-meters distance to LoRaWAN gateway, any brands on the market.

For Applications

Energy Monitoring, Fuel Monitoring, Process Monitoring, Smart Irrigation, Vehicle Tracking

LoRaWAN communication

LoRaWAN communication standard to allow sensor connect to any LoRaWAN Gateway on the market

Various fluid type monitoring

Monitored fluid types: diesel fuel, heating oil, motor fuel, other types of liquid fuels with kinematic viscosity from 1.5 to 6 mm2/s

Design for harsh environment

IP67 and durable housing for harsh environment of engine room/cabinet

Multi-parameter monitoring

Multi-parameter monitoring such as differential/supply/return flow, differential/supply/return volume, supply/return temperature

FLOW METER
Measurement fluids diesel fuel, heating oil, motor fuel, other types of liquid fuels with kinematic viscosity from 1.5 to 6 mm2/s
Measurement Range (L/h) 10-100, 20-250, 40-500
Measurement error+/- 1%
Max pressure, MPa 2.5
Nominal pressure, MPa 0.2
Kinematic viscosity, min/max, mm2/s 1.5/6.0
Solid particles size in liquid, mm <=0.015
COMMUNICATION
SF FactorsSF7∼SF12
AntennaInternal Antenna 2.0 dbi
Power supplyExternal power supply 10-48 VDC, avg 41 mA and max 66 mA @12 VDC
RF Frequency and Power860∼930MHz, 14∼20 dBm, configurable for zones: EU868, IN865, RU864, KR920, AS923, AU915, US915
ProtocolLoRaWAN, class A and class C
Data sending modesInterval time, magnetic key and alarm
RF Module complies toETSI EN 300 220, EN 303 204 (Europe) FCC CFR47 Part15 (US), ARIB STD-T108 (Japan)
Working temperature-40∼80℃ for flow meter and -40∼60℃ for LoRaWAN node
Dimensions and Net-weightH110xW73xD42, 250g (LoRaWAN Device Node) and H100xW180xD85 for 250 L/h flow meter
HousingPolycarbonate and Aluminum (wall mount bracket included), IP67

Dimension

Application Notes

Only available for Logged-in members.
Please Log in or Register to access this information.

Application: Identify the purpose (industrial, automotive, marine, etc.).
Flow Rate & Accuracy: Determine flow rate range and required accuracy.
Fluid Compatibility: Ensure compatibility with the fuel type.
Measurement Principle: Choose the appropriate type (e.g., turbine, ultrasonic).
Environmental Conditions: Evaluate temperature, pressure, and corrosive substances.
Installation: Consider space, pipe size, and orientation.
bottom of page