1. Introduction

Overview

Daviteq IEC485 Converter is to connect to RS485 IEC 62056-21 port of field slave device such as power meter, water meter, flow meters... The converter can be integrated into the wireless transmitter from Daviteq, such as Sub-GHz WS433, LoRaWAN WSLRW, and Sigfox WSSFC, to build the complete Wireless IEC485 master node. The converter is powered by external power.


Specification

Input port;1 x RS485 master port

Protocol;IEC 62056-21

Fault protected RS-485 bus pins;up to ±40V

HBM ESD protection on RS-485 bus pins;±15kV

Extend common mode range;±15V (larger than required for RS-485)

High transient over voltage tolerance;±60V

Full fail-safe RS-485 receivers;open, short, terminated

2. Principle of Operation

The operation principle for RS485 communication under the IEC 62056-21 standard:


Overview of IEC 62056-21 Standard

The IEC 62056-21 standard specifies a protocol for communication with utility meters, such as electricity meters. This protocol is designed to facilitate data exchange between a master device (like a computer) and a meter using various communication media, including RS485.


RS485 Communication

RS485 is a robust serial communication protocol widely used in industrial environments due to its ability to handle long-distance communication and resist electrical noise. It operates using differential signaling, which helps minimize the impact of noise on data transmission.


Key Principles

1. Communication Modes:

- Mode A to D: These modes use ASCII characters for communication, allowing straightforward data exchange.

- Mode E: This mode uses HDLC (High-Level Data Link Control) for more complex and secure data transmission.


2. Data Transmission:

- RS485 enables serial communication between the master device and the meter. It supports both half-duplex and full-duplex communication modes.

- Half-duplex: Data can be sent in one direction at a time, either from the master to the meter or vice versa.

- Full-duplex: Data can be sent and received simultaneously in both directions.


3. Baud Rates:

- The protocol specifies various baud rates to ensure compatibility with different devices. Common baud rates include 300, 600, 1200, 2400, 4800, 9600, and 19200 bits per second.


4. Data Readout and Programming:

- Data Readout Mode: This mode allows the master device to read data from the meter, such as consumption values, meter status, and other relevant information.

- Programming Mode: This mode enables the master device to configure and program the meter settings, such as tariff schedules, time synchronization, and other parameters.


Advantages of RS485:

- Long-Distance Communication: RS485 can handle communication over distances up to 1200 meters, making it ideal for large industrial setups.

- Noise Resistance: The differential signaling used in RS485 helps reduce the impact of electrical noise, ensuring reliable data transmission.

- Multi-Device Communication: RS485 supports communication with multiple devices on the same bus, allowing up to 32 devices to be connected.

3. Calibration

No calibration is required for IEC485 converter

4. Application Notes

!
Widget Didn’t Load
Check your internet and refresh this page.
If that doesn’t work, contact us.

5. Installation Notes

Installation notes for RS485 communication under the IEC 62056-21 standard:


General Setup

  1. Connection Ports: Ensure that the RS485 ports on both the master device and the meter are properly connected. Use shielded twisted-pair cables to minimize electrical noise.

  2. Baud Rates: Configure the baud rate settings on both devices to match. Common baud rates include 300, 600, 1200, 2400, 4800, 9600, and 19200 bits per second.

  3. Protocol Modes: Select the appropriate communication mode (A to E) based on your application needs. Modes A to D use ASCII, while mode E uses HDLC.


Wiring and Connections

  1. Differential Signaling: RS485 uses differential signaling, so ensure that the A and B lines are correctly connected. The A line should be connected to the positive terminal, and the B line to the negative terminal.

  2. Termination Resistors: Install termination resistors (typically 120 ohms) at both ends of the RS485 bus to prevent signal reflections.

  3. Grounding: Proper grounding is essential to avoid communication issues. Connect the ground of the RS485 network to a common ground point.


Device Configuration

  1. Addressing: Assign unique addresses to each device on the RS485 network to avoid conflicts.

  2. Wake-Up Sequence: For battery-powered meters, send a wake-up sequence before initiating communication. This typically involves sending a string of zero characters followed by a pause.

  3. Data Readout and Programming: Use the specified modes for reading data from the meter and programming meter settings. Ensure that the master device is configured to handle these operations correctly.


Testing and Troubleshooting

  1. Communication Test: Perform a communication test to verify that data is being transmitted and received correctly. Check for any errors or interruptions in the data flow.

  2. Error Handling: Implement error handling routines to manage communication failures or data corruption.

  3. Monitoring: Continuously monitor the RS485 network for any signs of issues, such as unexpected noise or signal loss.


Safety and Compliance

  1. Compliance: Ensure that all installations comply with relevant safety standards and regulations.

  2. Documentation: Keep detailed records of the installation process, including wiring diagrams, configuration settings, and test results.

6. Troubleshooting

Troubleshooting tips for RS485 communication under the IEC 62056-21 standard:


Common Issues and Solutions

1. No Data Received:

- Check Connections: Ensure all RS485 connections are secure and correctly wired. Verify that the A and B lines are properly connected.

- Baud Rate Mismatch: Confirm that the baud rate settings on both the master device and the meter match. Mismatched baud rates can prevent successful communication.

- Termination Resistors: Ensure termination resistors are installed at both ends of the RS485 bus to prevent signal reflections.


2. Data Corruption:

- Noise Interference: Use shielded twisted-pair cables to minimize electrical noise. Ensure proper grounding of the RS485 network.

- Differential Signaling: Verify that the differential signaling is functioning correctly. Check for any issues with the A and B lines.


3. Communication Failures:

- Address Conflicts: Ensure each device on the RS485 network has a unique address to avoid conflicts.

- Wake-Up Sequence: For battery-powered meters, send a wake-up sequence before initiating communication. This typically involves sending a string of zero characters followed by a pause.


4. Intermittent Connectivity:

- Cable Length: RS485 supports communication over long distances, but ensure the cable length does not exceed the maximum limit (typically 1200 meters).

- Environmental Factors: Check for environmental factors that might affect communication, such as extreme temperatures or electromagnetic interference.


Testing and Monitoring

1. Communication Test:

- Perform a communication test to verify data transmission and reception. Use diagnostic tools to check for errors or interruptions in the data flow.


2. Error Handling:

- Implement error handling routines to manage communication failures or data corruption. Ensure the system can recover from errors gracefully.


3. Continuous Monitoring:

- Continuously monitor the RS485 network for any signs of issues. Use monitoring software to track data flow and detect anomalies.


Additional Tips

1. Firmware Updates:

- Ensure that the firmware on both the master device and the meter is up to date. Firmware updates can resolve compatibility issues and improve communication stability.


2. Documentation:

- Keep detailed records of the installation and troubleshooting process. Document wiring diagrams, configuration settings, and test results for future reference.

7. Maintenance

Important troubleshooting tips for an IEC485 converter:


  1. Check Wiring and Connections:

    • Ensure all connections are secure and that A+ and B- communication cables are correctly connected throughout the network.


  2. Verify Termination Resistors:

    • Confirm that termination resistors (typically 120 ohms) are installed at both ends of the RS485 bus to prevent signal reflections.


  3. Inspect Grounding:

    • Proper grounding is essential to avoid ground loops and reduce noise. Check that the network is properly grounded.


  4. Check Communication Parameters:

    • Verify that all devices on the network are configured with the same baud rate, parity, stop bits, and data bits.


  5. Monitor for Noise and Interference:

    • Use twisted pair cables to minimize electromagnetic interference (EMI). Check for sources of electrical noise that could affect communication.


  6. Test with Known Good Devices:

    • Replace the RS485 transmitter with a known good device to determine if the issue is with the transmitter or another part of the network.


  7. Check for Biasing Resistors:

    • Ensure that biasing resistors are correctly installed if required by your network configuration.


  8. Review Device Configuration:

    • Confirm that each device has a unique address and that there are no address conflicts on the network.

8. Default Configuration

This IEC485 converter has the default configuration, however, those parameters can be changed. The user can change the configuration on the wireless transmitter so that the complete node(converter+ wireless) delivers the proper output value. Please check the Payload document for more information.