QUICK INSTALLATION GUIDE

1.1 Introduction

WSSFC-PPS is a Sigfox-ready integrated Process Pressure Sensor, and it has different kinds of measurements, such as Gage/Absolute/Sealed Gage, range -1∼1000 barg, high accuracy, and stability. The sensor will transmit data in kilo-meters distance to Sigfox base stations. WSSFC-PPS can support all regions of Sigfox network in over the World, RC1, RC2, RC3, RC4, RC5, RC6, RC7.

How the sensor connect to system?

The architecture of the Sigfox system
The architecture of the Sigfox system

System components:
  1. The end nodes are Sigfox-Ready Sensors or Actuators;

  2. The Sigfox Base Stations (installed and operated by Sigfox Operator);

  3. The Sigfox Back-End (Operated by Sigfox Company);

  4. The Application Server is the destination software users want to utilize the data from/to Sigfox-Ready sensors/ actuators.


How do you set up the Sigfox-Ready device and get its data to the Application Software? Please follow these steps:
  1. Contact the local Sigfox Operator to sign a Data plan contract. You will be provided an account;

  2. Log in to the Sigfox Back-end by your own account then add the Sigfox-Ready Devices. Please follow the guidelines of Sigfox back-end;

  3. Configure the callback or data forwarding from the Sigfox Back-end to the Application Software. Please follow the guidelines of Sigfox back-end;

  4. Once the payload is on the Application server, decode data from Payload. Please check Section 1.9 for the Payload document.

1.2 Application Notes

For Applications

Flood Monitoring, Fuel Monitoring, Level Monitoring, Process Monitoring, Safety Monitoring, Smart Irrigation, Water Pressure Pipeline Monitor

Notes

  • Sensor Materials Compatibility: Choose materials that won't react with the substances or degrade in corrosive media.

  • Environmental Conditions: Consider the system environment (pipes, vibrations, temperature, etc.).

  • Pressure Range: Choose sensors that function well within the process range.

  • Precision and Sensitivity: Determine the required level of precision and sensitivity.

1.3 When does device send Uplink messages?

The device will send uplink messages in the following cases:


  • Case 1: After power-up in the 60s, the device will send the first message called START_UP. The payload will tell the user the HW version, FW version, and current configuration of the device;


  • Case 2: Then, in every interval time (pre-configured), for example, 10 minutes, it will send the message called CYCLIC_DATA. The payload will tell the user the following data like measured values, battery level, and alarm status...

To change the cycle of data sending, you can change the value of the parameter: CYCLIC_DATA_PERIOD (default is 1800 seconds).

  • Case 3: If ALARM_ENABLED=1, the device will send ALARM message immediately when device switches from Normal state to Alarm state. It will repeat sending ALARM messages in predefined ALARM_PERIOD time interval (default is 10 minutes) if the Alarm state still exist;


  • Case 4: During the commissioning, testing, or calibration sensor, the user can force the device to send the uplink message to get the data immediately. This message is called FORCE_DATA. The payload will provide data like raw measured value, scaled measured values, battery level, and alarm status... It can be forced by applying the magnet key on the reed switch in 1s;


  • Case 5: If users want to change the configuration immediately, they don't need to wait until the next cyclic data-sending message; instead, they can force the device to send a special uplink message so that the device can get the new downlink message. This uplink message is named PARAMETERS_UPDATE. It can be forced by applying the magnet key in more than 5s.

  • Case 6: In every interval time (pre-configured), for example, 24 hours, it will send the message called HEARTBEAT. The payload will tell the user the following data like hardware version, firmware version, current sensor configuration


1.4 Default Configuration

This PPS pressure sensor has the default configuration, however, those parameters can be changed. The user can change the configuration on the wireless transmitter so that the complete sensor (transducer + wireless) delivers the proper output value. Please check the Payload document for more information.

1.5 Battery/ Power Supply

The Device uses below batteries:

  • Battery type: Primary battery

  • Battery size and Voltage: AA 1.5VDC

  • Number of batteries: 02

  • Recommended batteries: Energizer® L91 or equivalent from Duracell®;


Please take note on the Polarity of the batteries as below picture.



Understanding the Battery Levels:

  • Level 3 (4 bars): battery energy is 60-99%

  • Level 2 (3 bars): battery energy is 30-60%

  • Level 1 (2 bars): battery energy is 10-30%

  • Level 0 (1 bar): battery energy is 0-10%


Note: to display accurately the remaining energy of battery, please configure the correct BATTERY_TYPE by downlink type 5 or offline cable. Please check the section Principle of Operation for more details.


1.6 What's in the Package?



1.7 Guide for Quick Test

With the default configuration, the device can be connected quickly to the Sigfox Network by the following steps.


Step 1: Prepare the values of communication settings
  • Device ID: Get Devive ID on the device nameplate 

  • Device PAC: Get Devive PAC on the device nameplate 


Note: All Sigfox sensors are pre-configured with the correct RC before delivery. The settings of Device ID, Device PAC, and RC could also be read from the device memory map. Please reference Section 3.2 Sensor configuration for details.


Step 2: Add the device to the Sigfox Backend

Please refer to the below Section 1.10 for details.


Step 3: Install the batteries to the device

Please refer to Section 1.5 above for instructions on battery installation.

After installing the battery in 60 seconds, the first data packet will be sent to the Sigfox network. After receiving the first data packet, the time of another packet depends on the value of the parameter: CYCLIC_DATA_PERIOD. Additionally, you can use a magnet key to touch the magnetic switch point on the housing within 1 second to initiate force packet of the device to send data instantly and the LEDs on the housing will be lit with SKY BLUE color.


Note:

If the device is required to connect to the external power, the correct external power supply must be connected to the device power connector. Refer section 1.8 INSTALLATION for details of the power wiring


If the device is required to connect to external sensor, the connection must be implemented before power up. Refer section 1.8 INSTALLATION for details of the wiring


If device is required the calibration for correct measurement, the calibration must be implemented. Refer detail at section 3.3 Calibration/ Validation.


Step 4: Decode the payload of the receiving package

Please refer to Section 1.9 Payload Document and Configuration Tables for details of decoding the receiving packet to get the measured values.

1.8 Installation

Dimension Drawings and Installation Gallery (Photos and Videos)

Please follow the checklist below for a successful installation:

1. Have you studied the dimensions of the device as above drawings?
 

2. Have you tested and make sure the device have been connected successfully as Section "1.7 Guide for Quick Test" above?
 

3. Have the device been configured properly as per Section 3.2 below?
 

4. Have the device been calibrated or validated as per Section 3.3 below?
 

5. Then you can start to install the device at site. Please check the following Installation Notes for Sensor Part (if available) before installation.

Installation Notes for Sensor Part (if available)
  • Please do not hold the upper housing to install the sensor; it will cause the sensor probe to disconnect from the electronics housing.

  • Only use a wrench to turn the process connection part of the sensor to install or remove.


Installation Guide for Main Device

Check the Location for the best RF Signal

Make sure the site is good enough for RF signal transmission.


Tip: To maximize the transmission distance, the ideal condition is Line-of-sight (LOS) between the device (wireless part) and the Base station. In real life, there may be no LOS condition. However, the device still communicates with the Base station, but the distance will be reduced significantly.


DO NOT install the wireless sensor or its antenna inside a completed metallic box or housing because the RF signal can not pass through the metallic wall. The housing is made from Non-metallic materials like plastic, glass, wood, leather, concrete, and cement… is acceptable.


Mounting the Device on the Wall or Pole

Mount the sensor onto a wall by the mounting bracket as below pictures



1.9 Payload Document and Configuration Tables

Please click below button for:
 

  • Payload decoding of Uplink messages;

  • Payload encoding of Downlink messages;

  • Configuration Tables of device.

​​

Note:

If the content of below web payload, memory map, and sample decoder could not be copied, please install the extension of "Enable Copy Paste - E.C.P" for Microsoft Edge and for Google Chrome.

1.10 How to connect device to Back-end/ Network Server/ Coordinator

This instruction is applied to all kinds of Sigfox-Ready sensor produced by Daviteq.


Step 1: Log in to the sigfox backend website


Step 2: Click on Device


Step 3: Click New → Select a group


Step 4: Fill in the required information


Note: Some of our products may not have end product certification in time, to add the product to Backend Sigfox please follow the steps below.


Click on the text as shown below


Check the box as shown below to register as a prototype


2
MAINTENANCE

2.1 Troubleshooting

Please find below the steps to identify the problems from the Communication Part or Sensor Part:

  • If the device cannot connect to the Gateway, or System, or Coordinator the first time, it is the Communication Problem;


  • If the device status like battery, RSSI level, data status, or other communication is normal, but the measured values are not updated or wrong, it would be the problems of the Sensor part;


  • If the data coming to the gateway, system, or coordinator is not frequent as expected, the problem would be Communication.


Please refer to the troubleshooting guide for the Communication and Sensor Part below.

Troubleshooting for Communication



Troubleshooting for Sensor Part (if available)

1. The measured value is not within the expected value

  • The sensor is drifted over time: Re-calibrate the sensor.

  • The sensor was spoiled due to some reason or the water hammer effect: Replace the new sensor


2. The measured value is always zero or near zero

  • There could be leakage so that the pressure is not contained: check the leakage of piping or process connection of the sensor.

  • The sensor was removed from the process: Please check the sensor installation.


3. HW_Error = 1

  • Loosed connection of sensor module and wireless transmitter: Check the internal wiring.

  • The sensor module got a problem: Please consult the manufacturer for a warranty or replacement.

2.2 Maintenance

Maintenance for Main device

There is no requirement for maintenance of the Hardware of this Sigfox-Ready device except:


1. The battery needs to be replaced. Please check the battery status via uplink messages;


Note: When the battery indicator shows only one bar (or 10% remaining capacity), please arrange to replace the battery with a new one as soon as possible. If not, the battery will drain completely, and the resulting chemical leakage can cause severe problems with the electronic circuit board.


2. Sensor, please refer to the maintenance section of the sensor document.

Maintenance for Sensor part (if available)

Re-calibration: Approx. 12-24 months

The pressure sensor may be drifting over time.

3
ADVANCED GUIDE

3.1 Principle of Operation

Principle of Operation for Device WSSFC-PPS | FW1


The Daviteq Sigfox Pressure (PPS) Sensor comprises 02 parts linked internally:

  • The Daviteq Sigfox wireless transmitter;

  • The Daviteq PPS pressure sensor.


What are the primary output values?

  • Pressure: The measured process pressure value.This parameter is used for alarm. This parameter in the payload is PRESSURE

  • Temperature: Measured process temperature value (oC). This value equals TEMPERATURE_X10 (in the payload) divided by 10.

  • Alarm Status: Alarm when main parameter (PRESSURE) is out of pre-configured thresholds. This parameter in the payload is ALARM

  • Number of Consecutive Alarm/Cyclic: The number of consecutive alarm or consecutive cyclic payload. This parameter in the payload is TENTATIVE. TENTATIVE will be reset to 0 when previous payload is cyclic message and current payload is alarm message OR vice versa. If the number of Consecutive Alarm/Cyclic are greater than 255, the TENTATIVE keeps the value of 255.

Please check the payload document for more details.

What are the secondary output values?

Below output values are useful for device maintenance and troubleshooting.


  • Battery level (%): to understand the remaining capacity of the battery. This parameter in the payload is BATTERY_LEVEL.

  • Sensor error code: to understand whether the sensor is working properly or not. This parameter in the payload is HW_ERROR

  • Sensor current configuration: to understand what is the current setting of the sensor. This parameter in the payload is LASTEST_SIGFOX_DONWLINK

  • Hardware version and Firmware version: to understand the product version: parameter in the payload is HW_VERSION and FW_VERSION


Principle of operation

Most of the time, the Sigfox device will be in sleep mode. When the timer reaches the Measure_Period (for example, 2 minutes), it will wakes up the device to start the measurement.

*** This Measure_Period will affect the energy consumption of the device.


The measurement will take a certain time to finish; it can take milliseconds or seconds to finish the measurement. This measurement time depends on sensor type, required accuracy, and other factors. Shorter measurement time, lower energy consumption, and longer battery life.


After finishing the measurement cycle, the device can read the pressure (PRESSURE)


If parameter ALARM_ENABLE = 1

Then the device will compare the PRESSURE value with the Low Alarm Setpoint and High Alarm Setpoint.




After comparison, the devices will have 03 statuses:

  • No_Alarm;

  • Low_Alarm

  • High_Alam.


How the device send uplink message base on above 03 states?


If Device state is No_Alarm, it will check the timer to reach the Cyclic_Data_Period to send the CYCLIC_DATA uplink message;


If Device state is changed from No_Alarm to Low_Alarm or Hi_Alarm, it will send alarm message immediately. Please check the below picture to understand the operation flow when finishing the measurement cycle:



Once alarm happened and send the first alarm message, the device will send the next alarm message in the Alarm_Period if the device is still in Alarm states (Low_Alarm or High_Alarm). Please check below picture to understand the operation flow when the Alarm timer reaches the Alarm_Period.



If parameter ALARM_ENABLE = 0

The device will check the timer to reach the Cyclic_Data_Period to send the CYCLIC_DATA uplink message;

Please check the Payload document to understand clearly about uplink messages, downlink messages, meaning of parameters for configuration...

Principle of Operation of Sensor part (if available)

A Piezo pressure sensor is a device that utilizes the piezoelectric effect to measure and convert mechanical pressure into an electrical signal. The piezoelectric effect refers to the ability of certain materials to generate an electric charge when subjected to mechanical stress or pressure.


The principle operation of a piezo pressure sensor involves the following steps:

  1. Piezo-electric Material: The sensor consists of a piezoelectric material, typically a ceramic material such as quartz or piezoelectric crystals like lead zirconate titanate (PZT). These materials have the property of generating an electric charge when subjected to pressure or stress.

  2. Sensing Element: The piezoelectric material is shaped into a sensing element, usually in the form of a thin disc or a diaphragm. The sensing element is designed to be mechanically sensitive to pressure changes. When pressure is applied to the sensing element, it undergoes deformation or displacement, causing mechanical stress in the piezoelectric material.

  3. Generation of Electric Charge: The mechanical stress or pressure applied to the piezoelectric material causes it to generate an electric charge. This charge is proportional to the magnitude of the applied pressure. The piezoelectric material acts as a transducer, converting the mechanical pressure into an electrical signal.

  4. Electrodes: The piezoelectric material is sandwiched between two electrodes, typically made of metal. These electrodes serve as electrical contacts to collect the electric charge generated by the piezoelectric material. One electrode is connected to the positive terminal, and the other electrode is connected to the negative terminal of the measurement circuit.

  5. Measurement Circuit: The electrical signal generated by the piezoelectric material is captured and processed by a measurement circuit. The circuit may include amplifiers, filters, and signal conditioning components to optimize the signal quality and make it suitable for measurement or further processing.

  6. Output: The output of the measurement circuit can be in the form of a voltage or current signal, which represents the pressure applied to the sensor. This output can be displayed, recorded, or used for control purposes in various applications.

Default Configuration Parameters of Sensor part (if available) 

This PPS pressure sensor has the default configuration, however, those parameters can be changed. The user can change the configuration on the wireless transmitter so that the complete sensor (transducer + wireless) delivers the proper output value. Please check the Payload document for more information.

3.2 Configuration

How to configure the device?

Sensor configuration can be configured in 02 methods:

Method 1: Configuring via Downlink messages.

Method 2: Configuring via Offline cable.


Note: The sensor is only active for offline configuration in the first 60 since power up by battery or plugging the configuration cable.


Which Parameters are configured?

Please check Part G in Section 1.9 Payload Documents above.

Method 1: Configuration via Downlink messages

Please check the Part D & E in Section 1.9 Payload Documents above.

Method 2: Configuration by Offline Cable

Please download the Configuration Template File of this sensor to be used in Step 4 below.

Instructions for offline configuration of the Daviteq LoRaWAN sensors. Please follow the following steps.


Note: The sensor is only active for offline configuration in the first 60 since power up by battery or plugging the configuration cable.


1. Prepare equipment and tools

The following items must be prepared for configuration.

  • A PC using the Windows OS (Windows 7 or above versions). The PC installed the COM port driver of the Modbus configuration cable (if needed). The driver is at link: Modbus Configuration Cable COM port driver for PC and the instruction to install  the driver at link: How to install the driver.

  • A Modbus configuration cable 

  • Tools to open the plastic housing of LoRaWAN sensors (L hex key or screwdriver)


2. Download and launch Daviteq Modbus configuration software 
  • Click the link below to download Daviteq Modbus configuration software:

https://filerun.daviteq.com/wl/?id=yDOjE5d6kqFlGNVVlMdFg19Aad6aw0Hs

After downloading the software, unzip the file named: Daviteq Modbus Configuration.zip and then copy the extracted folder to the storage drive for long-term use. 

  • Open the folder, double click on the file Daviteq Modbus Configuration Tool Version.exe to launch the software and the software interface as below:


Note: The software only runs on Microsoft Windows OS (Windows 7 and above).


3. Connect the cable and configure the sensor

Step 1: 

Connect the PC to the sensor using the configuration cable.

- Use the configuration cable (Item code: TTL-LRW-USB-01).


- Connect the USB-A plug into the USB-A socket of the PC.


Step 2: 

On the configuration software, choose the relevant Port (the USB port which is the cable plugged in) and set the BaudRate: 9600, Parity: none


Step 3:

Click Connect button to connect the software to the sensor. After successful connection, the Connected status will show on the software.


Step 4: 

Import the configuration template file of the sensor (as above link) to the software: click menu File/ Import New and then browse the relevant sensor template file (csv file) and click Open to import the template file.


Note: The sensor is only active for configuration for 60 seconds since plugging the configuration cable or the power supply into the sensor.

Each sensor type has its own template file. Refer to the sensor's manual to download the correct file.


Step 5:

Open the housing of the sensor and quickly plug the connector of the configuration cable into sensor's modbus configuration port as below figure. After plugging the connector, the software will read the parameter values automatically.

Plug the cable connector into sensor's modbus configuration port. This port is located at a different location, depends on the sensor type.


Note: If the sensor has SKU of WSSFCEX-PPS and hardware version 1 &2, the sensor must be powered by batteries for configuration


Step 6: 

Read the current value of the parameter with Modbus Function 3

  • At the relevant row of the parameter, check box 3 on column Func to read the value of the parameter. The read value is shown in VALUE ON MEMMAP column.


The sensor is only active for configuration for 60 seconds since plugging the configuration cable or the power supply into the sensor. After 60 seconds, the TIME_OUT text will show on EXCEPTION column of the software.


Step 7: 

Write the new setting to the parameter with Modbus Function 16

  • Double click on the column VALUE TO WRITE of the parameter and input the new setting value of the parameter;

  • Uncheck the tick on the FC column of the parameter, click on the arrow, select 16 and then check on the FC column to write a new setting to the parameter. The WRITE_OK text will show on EXCEPTION column if the software successfully writes the setting.


Repeat Step 6 to read the setting of the parameter for double-checking.


Note: For some critical parameters of the sensor, the password in "password for setting" must be written before writing the new settings to these parameters.

Only read/ write registers are allowed to write.

The sensor is only active for configuration for 60 seconds since plugging the configuration cable or the power supply into the sensor. After 60 seconds, the TIME_OUT text will show on EXCEPTION column of the software.


4. Troubleshooting

3.3 Calibration/ Validation

How to force sensor to send data for calibration/ validation (if available)

By using the magnet key, the Sigfox node can be triggered to send data to base station immediately. There will be a beep sound from the buzzer meaning the data has been sent (Buzzer will be updated in the latest version).



Note:

Once sending the data to base station by the magnet key, the timer of sending time interval will be reset;

The shortest time interval between the two manual triggers is 15s. if shorter than 15s, there will be no data sending.


Calibration/ Validation sensor (if available)

It is recommended to recalibration the sensor in the interval of 12∼24 months by using a pressure calibrator to generate the standard pressure to apply to the sensor. Please check the below picture.


The hand pump is a pressure generator. The Fluke is a high accuracy pressure sensor to measure the actual pressure generated by the hand pump.


To calibrate, generate 2 pressure points within the measuring range of the sensor:

  • Low-pressure point, for example: 1 barg

  • High-pressure point, for example: 10 barg


Record the reading values corresponding to those 2 pressure points. Then calculating the new scaling factor A & B.


Using an offline tool or downlink message (check the Payload document) to write the new A & B factors to the sensor.

4
PRODUCT SPECIFICATIONS

4.1 Specifications

SensorAdvanced PIEZO technology
Measurement rangeSelect from -1∼1000 bar Gage/Absolute/Sealed Gage
Over pressure protection1.5 x Span
Accuracy & Stability0.25% or 0.5% of span, < 0.2% span/ year
Wetted parts304SS/316SS
Measuring FluidsAny fluid which is workable with materials 304SS/316SS
Working temperature-20∼80℃
Compensation temperature-10∼50℃
Process connectionStandard G 1/4 or Others (consult factory)
COMMUNICATION
Sigfox zonesRC1∼RC7
AntennaInternal Antenna 2.0 dbi
Battery02 x AA Type 1.5VDC, working time up to 10 years (depends on configuration)
RF Module complies toCE, FCC, ARIB
Working temperature-40∼60℃ (using Energizer® Lithium Ultimate AA battery)
DimensionsH180xW50xD40
Net-weight250g
HousingPolycarbonate & POM plastic, IP68

5
WARRANTY & SUPPORT

5.1 Warranty

Warranty

Below terms and conditions are applied for products manufactured and supplied by Daviteq Technologies Inc.


Free Warranty Conditions
  1. The manufacturer undertakes to guarantee within 12 months from shipment date.

  2. Product failed due to defects in material or workmanship.

  3. Serial number, label, warranty stamp remains intact (not purged, detected, edited, scraped, tore, blurry, spotty, or pasted on top by certain items).

  4. During the warranty period, if any problem of damage occurs due to technical manufacturing, please notify our Support Center for free warranty consultancy. Unauthorized treatments and modifications are not allowed.

  5. Product failed due to the defects from the manufacturer, depending on the actual situation, Daviteq will consider replacement or repairs.


Note: One way shipping cost to the Return center shall be paid by Customers.


Paid Warranty
  1. The warranty period has expired.

  2. The product is not manufactured by Daviteq.

  3. Product failed due to damage caused by disasters such as fire, flood, lightning or explosion, etc.

  4. Product damaged during shipment.

  5. Product damaged due to faulty installation, usage, or power supply.

  6. Product damage caused by the customer.

  7. Product rusted, stained by effects of the environment or due to vandalism, liquid (acids, chemicals, etc.)

  8. Product damage is caused by unauthorized treatments and modifications.


Note: Customers will be subjected to all repairing expenses and 2-way shipping costs. If arises disagreement with the company's determining faults, both parties will have a third party inspection appraise such damage and its decision be and is the final decision.


5.2 Support

Support via Help center

If you need our support for Daviteq device's installation, configuration, test, and decode, please email us at: support@daviteq.com OR input support request at link: https://forms.office.com/r/XWHbYG7yy7

Our support engineer will contact you via email or the support ticket system.

 

If you have any questions about the product, you can search for information on our web (https://www.iot.daviteq.com/). If you can't find the right information, please register an account and send us a request at link Contact us | Daviteq Technologies . We will respond within 24 hours.