1. Giới thiệu

Overview

BV is a Mini Control Valve, integrated with a Ball valve body. The BV can be integrated into the wireless transmitter from Daviteq, such as Sub-GHz WS433, LoRaWAN WSLRW, and Sigfox WSSFC, to build the complete Wireless relay output node. The BV is also powered by the batteries or external power. Mini Control valve is the best choice for an Irrigation System for a Garden, Smart Farm, or Hydroponic Farm. It can be used for FCU in HVAC or any water supply line in a Facility or Building.


Specification

Valve Body: Ball valve, low torque design

Body materials: Brass (standard), 304SS, 316SS

Sealing: EPDM (standard), NBR, Silicone Rubber

Seat: PTFE

Ball: 304SS (standard), 316SS

Size: DN8, DN15, DN20, DN25

Process connection: BSPP female threads

Cable: 2m molded M12 connector cable

Working temperature: 0∼100℃

Working pressure: -1∼10 barg

Manual override: Yes

Valve housing rating: IP5

Control functions: On-Off

Valve Diagnostic: Yes, to detect clogging, longer closing or opening time, valve failure

2. Nguyên tắc hoạt động

This mini-control valve is a 2-piece design ball valve with a low torque feature to allow the valve to use less energy than the regular valve on the market. This feature allows the valve to be operated by batteries for years.


The ball will be moved by the internal micro motor and a set of micro limit switches to allow the running from 0° to 90° of opening.


The valve will be powered and controlled from a wireless device, it could be LoRaWAN, Sigfox, NB-IoT, or Sub-GHz technology.

3. Hiệu chuẩn

The mini-control valve is calibrated at the factory to make sure it will close or open completely.

However, after time of usage, the closing and opening times will be increased a bit due to the friction between the ball and the seat increase. Users can check these values from the diagnostic feature of the device and adjust accordingly. Users can use the offline tool or downlink to write the new values of maximum allowable valve open time and maximumu allowable valve close time

4. Ghi chú ứng dụng

5. Installation Notes


6. Troubleshooting

1. Valve take longer time to open and close

  • Check inside status of valve

  • Check fluid pressure

  • Check voltage of power supply for actuator mechanism


2. Valve could not be open and close completely

  • Check any object stuck inside the valve

  • Check the ball erosive wear, ball deformation


3. Valve could not open/close as control command

  • Check object that could lock the ball of the valve

  • Check cable from control module to valve

7. Maintenance

Re-calibration:

Once the error code appears on the system, please perform the calibration of opening and closing time to make sure the valve opens and closes completely, and no passing problem happens.


Valve body replacement:

Replace the new valve body.

8. Cấu hình mặc định

This device has the default configuration (opening and closing times), however, those parameters can be changed. The user can change the configuration on the wireless transmitter so that the complete sensor (transducer + wireless) delivers the proper output value. Please check the Payload document for more information